 序号  | 
 名称型号  | 
 型号规格  | 
 技术参数  | 
 备注  | 
| 
 1.1.1  | 
 干式电力变压器 
SCB9–□□□/10 
额定容量:30~2500KVA  | 
 SCB9-100/10  | 
 额定容量:100KVA;额定电压:10±2×2.5%/0.4KV;A组:空载0.45+15%负载1.67+15%总损耗2.12+10%;空载电流1.8+30%短路阻抗:4±10%;绕组温:100K;声功率级:65dB  | 
 B组:空载0.41+15%负载1.8+15%总损耗2.11+10%;空载电流1.7+30%  | 
| 
 1.1.2  | 
 SCB9-315/10  | 
 额定容量:315KVA;额定电压:10±2×2.5%/0.4KV;空载0.99+15%负载3.67+15%总损耗4.66+10%;空载电流1.2+30%短路阻抗:4±10%;绕组温:100K;声功率级:69dB  | 
 B组:空载0.88+15%负载3.9+15%总损耗4.78+10%;空载电流1.1+30%  | 
| 
 1.1.3  | 
 SCB9-630/10  | 
 额定容量:630KVA;额定电压:10±2×2.5%/0.4KV;空载1.51+15%负载6.22+15%总损耗7.73+10%;空载电流1.0+30%短路阻抗:4±10%;绕组温:100K;声功率级:71dB  | 
 B组:空载1.35+15%负载6.78+15%总损耗8.13+10%;空载电流0.9+30%  | 
| 
 1.1.4  | 
 SCB9-800/10  | 
 额定容量:800KVA;额定电压:10±2×2.5%/0.4KV;空载1.71+15%负载7.36+15%总损耗9.07+10%;空载电流1.0+30%短路阻抗:6±10%;绕组温:100K;声功率级:72dB  | 
 B组:空载1.54+15%负载7.8+15%总损耗9.34+10%;空载电流0.9+30%  | 
| 
 1.1.5  | 
 SCB9-1000/10  | 
 额定容量:1000KVA;额定电压:10±2×2.5%/0.4KV;空载1.99+15%负载8.61+15%总损耗10.6+10%;空载电流1.0+30%短路阻抗:6±10%;绕组温:100K;声功率级:72dB  | 
 B组:空载1.75+15%负载9.25+15%总损耗11+10%;空载电流0.9+30%  | 
| 
 1.1.6  | 
 SCB9-1250/10  | 
 额定容量:1250KVA;额定电压:10±2×2.5%/0.4KV;空载2.35+15%负载10.26+15%总损耗12.61+10%;空载电流1.0+30%短路阻抗:6±10%;绕组温:100K;声功率级:74dB  | 
 B组:空载2.03+15%负载11+15%总损耗13.03+10%;空载电流0.9+30%  | 
| 
 1.1.7  | 
 SCB9-1600/10  | 
 额定容量:1600KVA;额定电压:10±2×2.5%/0.4KV;空载2.76+15%负载12.4+15%总损耗15.16+10%;空载电流1.0+30%短路阻抗:6±10%;绕组温:100K;声功率级:75dB  | 
 B组:空载2.7+15%负载13.5+15%总损耗16.2+10%;空载电流0.9+30%  | 
| 
 1.1.8  | 
 SCB9-2000/10  | 
 额定容量:2000KVA;额定电压:10±2×2.5%/0.4KV;空载3.4+15%负载15.3+15%总损耗18.7+10%;空载电流0.8+30%短路阻抗:6±10%;绕组温:100K;声功率级:77dB  | 
 B组:空载3.0+15%负载16.2+15%总损耗19.2+10%;空载电流0.7+30%  | 
| 
 1.1.9  | 
 SCB9-2500/10  | 
 额定容量:2500KVA;额定电压:10±2×2.5%/0.4KV;空载4.0+15%负载18,18+15%总损耗22.18+10%;空载电流0.8+30%短路阻抗:6±10%;绕组温:100K;声功率级:78dB  | 
 B组:空载3.5+15%负载19.5+15%总损耗23+10%;空载电流0.7+30%  |